Adichandra Putra Ariesta, . (2026) SIMULASI PERBANDINGAN KINERJA MEKANISME FAULT RIDE THROUGH BERBASIS KONTROL PI DAN MPC PADA SISTEM PLTS TERHUBUNG GRID PADA KONDISI LOW VOLTAGE RIDE THROUGH. Skripsi thesis, Universitas Pembangunan Nasional Veteran Jakarta.
|
Text
ABSTRAK.pdf Download (120kB) |
|
|
Text
AWAL.pdf Download (1MB) |
|
|
Text
BAB 1.pdf Restricted to Repository UPNVJ Only Download (156kB) |
|
|
Text
BAB 2.pdf Restricted to Repository UPNVJ Only Download (860kB) |
|
|
Text
BAB 3.pdf Restricted to Repository UPNVJ Only Download (691kB) |
|
|
Text
BAB 4.pdf Restricted to Repository UPNVJ Only Download (22MB) |
|
|
Text
BAB 5.pdf Download (118kB) |
|
|
Text
DAFTAR PUSTAKA.pdf Download (156kB) |
|
|
Text
DAFTAR RIWAYAT HIDUP.pdf Restricted to Repository UPNVJ Only Download (94kB) |
|
|
Text
LAMPIRAN.pdf Restricted to Repository UPNVJ Only Download (8MB) |
|
|
Text
HASIL PLAGIARISME.pdf Restricted to Repository staff only Download (30MB) |
|
|
Text
ARTIKEL KI.pdf Restricted to Repository staff only Download (774kB) |
Abstract
Voltage sag disturbances in grid-connected photovoltaic (PV) systems can reduce active power transfer, destabilize the dc-link voltage, and impair inverter operation when adequate Fault Ride Through (FRT) capability is not implemented. This study analyzes and compares the performance of Proportional–Integral (PI)- and Model Predictive Control (MPC)-based FRT strategies under Low Voltage Ride Through (LVRT) conditions. A 100-kW, three-phase, 400-V grid-connected PV system was modeled and simulated in MATLAB/Simulink under symmetrical voltage sags of 0.8, 0.6, 0.3, and 0.07 p.u., each lasting 400 ms. Performance was evaluated in terms of recovery settling time, dc-link voltage overshoot, reactive power injection, Total Harmonic Distortion (THD), and LVRT compliance. The system without FRT failed to recover under all sag conditions. PI-FRT recovered at 0.8 and 0.6 p.u. with settling times of 60.40 and 72.42 ms, respectively, but failed at 0.3 and 0.07 p.u. MPC-FRT successfully recovered under all scenarios with settling times of 51.01, 62.46, 692.19, and 744.97 ms, respectively. MPC-FRT also achieved a lower average THD of 0.20% compared with 3.04% for PI-FRT and exhibited lower dc-link overshoot in three of the four scenarios. Therefore, MPC-FRT provides more consistent and reliable LVRT performance for grid-connected PV systems.
| Item Type: | Thesis (Skripsi) |
|---|---|
| Additional Information: | [No.Panggil: 2210314099] [Pembimbing 1 : Ferdyanto] [Pembimbing 2 : Luh Krisnawati] [Penguji 1: Achmad Zuchriadi] [Penguji 2: Nur Fauziyah] |
| Uncontrolled Keywords: | Fault Ride Through; Low Voltage Ride Through; Model Predictive Control; Grid-Connected PV System; Voltage sag. |
| Subjects: | T Technology > TK Electrical engineering. Electronics Nuclear engineering |
| Divisions: | Fakultas Teknik > Program Studi Teknik Elektro (S1) |
| Depositing User: | ADICHANDRA PUTRA ARIESTA |